Automation stations PXC4.E16
PXC4.E16 variants PXC4.E16S PXC4.E16 Order number S55375-C108 1) S55375-C100 1) Number of inputs and outputs (Onboard) 16 16 Number of universal inputs and outputs (UIO) 12 12 Number of relay outputs (DO) 4 4 Number of inputs and outputs (Onboard + TXM) up to 40 up to 40 Number of integration data points (Modbus TCP and / or RTU) 0 up to 40 Total number TXM-I/Os and integration DPs 40 80 2) Number of KNX PL-Link devices 0 up to 64 Number of configurable RS485 interfaces for Modbus RTU integration 0 1 Number of BACnet/SC nodes connected to PXC4.E16/PXC4.E16S acting as hub 0 (node only) 0 (node only) 1) For details on engineering, see PXC4, PXC5 & PXC7 Planning overview, A6V13054435. 2) KNX PL-Link data points do not count as integration points. For KNX PL-Link, only the limits on BACnet objects is considered. UIO Universal inputs and outputs support the following signal types: ● Passive sensors LG-Ni 1000, 2x LG-Ni1000, Pt 1000 (375, 385), NTC 10k (Type II / Beta (0-50 °C) = 3892 K), NTC 100k ● Resistance sensors 1000 Ohm, 2500 Ohm, 1000...1175 Ohm (for setpoint shift) ● Voltage input analog DC 0…10 V ● Current measurement analog DC 0...20 mA or 4...20 mA, (inputs U1, U2, U7, U8) ● Binary potential-free contacts for signaling functions ● Counter to 25 Hz (electronic switch to 100 Hz) ● Analog outputs DC 0…10 V DO Relay outputs for binary controls, changeover contact (NO, NC, pulse)